Single phase DC voltage transducer
This device is a kind of DC voltage isolation transducer, adopts principle of electromagnetic isolation, can sample the DC voltage, and isolated output standard signals, electrical isolation between input and output, and completely linear relationship between output signal and input signal. Can widely used in real-time monitoring/monitoring of DC voltage signals, industrial control, PLC measurement and control, and a variety of automatic control system.
Data Sheet
Test conditions: auxiliary power supply: +12V, room temperature: 25℃.
Input range: 0~0.1V~300VDC;
Output: 0~5VDC, 0~10VDC, 0~20mADC, 4-20mADC,frequency(0~5KHz、0~10KHz);
Auxiliary power supply: 12VDC, 15VDC, 24VDC optional;
Accuracy: class 0.2;
Load capacity: Load ≥2KΩ (voltage output), load≤250Ω(current output);
Temperature drift: class 0.2 = 200ppm/℃ ;
Isolation voltage: 2500 V DC;
Response time: ≤15 mS;
Rated power consumption: voltage output≤400mW, current output≤800mW;
Output ripple: ≤10mV;
Surge impact immunity:
Power port three–level ±0.5KV(L-N/2Ω/ integrated wave),
Analog I /O port three-level ±0.5KV (L-N/40Ω/integrated wave);
Pulse group immunity: Input / power port ± 2KV Analog I / O port ± 1KV;
Input overload capacity: 2 times rated input value;
Operating condition: temperature: -10~60℃;
Storage condition: -40~+70℃.
MH2 case
H2 case pin welding or screw installation plan
Wiring diagram of CE-VZ02-3*MH2,CE-VZ02-8*MH2 with voltage output
Wiring diagram of CE-VZ02-4*MH2,CE-VZ02-5*MH2 with current output
Pin mounted on the PCB easy to install;
High precision, low temperature drift;