Two Phase AC Current Transducer
This product is a two phase AC current tracking isolation transducer, real-time measurement and tracking of power grids or circuits AC current signals, output signal is 0-5V AC tracking signal. Applicable to power equipment, power grid monitoring system, railway signal system, etc.
Data Sheet* Test conditions: auxiliary power supply:+24V, room temperature:25℃
* Accuracy: class 0.5;
* Auxiliary power supply: DC +24V;
* Input range: 0~1A AC;
* Input frequency: 1700Hz~2600Hz;
* Output: 0~5V AC;
* Load capacity: Load≥2KΩ;
* Power frequency difference: 35’;
* Temperature drift: ≤200ppm/℃;
* Isolation voltage: DC 2500 V;
* Response time: ≤100 mS;
* Rated power consumption: ≤0.5W;
* Output ripple: none;
* Frequency range: 45~65Hz(up to 5K, please specify when ordering);
* Surge impact immunity:
Power port four-level 4000V, analog I/O port three-level 2000V
* Input overload capacity: 20 times of the measured current nominal value (maximum is 500A, applying a repetition of five times a second, interval 300S);
*Operating condition: -10℃~+60℃;
*Storage condition: temperature: -55~65℃; humidity: ≤95% (no dew).
S3 style product outline drawing
Installation dimensions
Connection diagram
High precision, low temperature drfit.
Small size, high reliability.
Fast response,wide frequency response.