DC multi-parameter digital transducer
HOME > Multi-parameter > DC Multi-parameter Digital Transducer

This product is a 1-phase DC power acquisition measurement intelligent isolation transducer. It can measure the current, voltage, power and electrical of the DC circuit. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 1000: 1. Hall measurement principle or resistance sampling measurement principle is with high accuracy, good stability and high communication speed, the completely isolated processing technology is with anti-interference ability. Measurement of electricity parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields.
Serial number | Item | Date | Unite | Remarks |
1 | Accuracy | 0.5,1.0 | % | Terminal input is 0.5, hole-thru. input is 1.0 |
Input range | MS3 case:500V*5A; ES5 case:1000V*1000A; MS5 case:1000V*5A; | The maximum range for each specification | ||
2 | Baud rate | 115.2K, 57.6K, 38.4K, 19.2K, 9600(default) 4800, 2400, 1200 | bps | Factory default communication format: 9600, N / 8/1, address 1; S5 type up to 19.2K; |
Communication | RS-485(twisted pair line) , RS-232C(treble line, only for N style parts) | RS422 optional | ||
Parity | None, Even, Odd, Space | |||
Max. number of nodes | 64 | node | Only for RS-485 | |
Bus protection | 400W transient voltage | ESD protection and thermosnap | ||
3 | A/D SPEED | 100 | mS | |
4 | Working temperature | -20℃~+60℃ | ||
5 | Isolation voltage | Input/output: 2500V DC for 1 min Input/power supply:2500V for 1 min Output/power supply:2500V for 1 min |
V
| The double isolation part numbers, their output and power supply are grounded together , there is only between the input and output isolation voltage |
6 | Overload | 2 x voltage span 1 sec. 10 for times with interval of 10 sec. 10 x current span for 1 sec. 5 times with an interval of 300 sec (only for hole thru. parts) | The input outside the linear range will result in poor accuracy | |
7 | MTBF | >30000 | hour | |
8 | Auxiliary power supply | +5V/+12V/+24V/+48V/ AC220V | V | 220VAC,DC only for N case parts |
9 | Power consumption | ≤250mW(+12V),≤500mW(+24V) | mW | Power consumption depends on power supply to be used |
10 | Temperature drift | ≤300 | ppm/℃ | (-20℃~+60℃) |
CE-AD11-**MS3 Case Type
CE-AD11-**MS3 Installation Diagram
CE-AD11-**ES5 Case Type
CE-AD11-**ES5 Installation Diagram
CE-AD11-**MS5 Case Type
CE-AD11-**MS5 Installation Diagram
Terminal definition and connection diagrams
Connection diagram shown in figure 6.1 (Note: 3and 4 terminal for the common ground)
Wiring diagram of CE-AD11-**MS3 product (Note the current access direction).
(Terminal 7 output is +5 V to provide 5V output (<20mA), the output and power are grounded together).
When the S3 case DC current is greater than 5A, external shunt input wiring diagram is shown in Figure 6.2; (Note terminal 3 and 4 for the common ground).
Wiring diagram of CE-AD11 - ** MS3 product (external shunt input for currents greater than 5A).
Refer to figure 6.3 for the wiring diagram of the S5 case. Current hole-thru input is maximum 1000A, when the current input from the terminal 5 and 6, the current should be ≤ 5A.
Wiring diagram of CE-AD11-**ES5
² Available with wide power supply: DC: 10-30V or 10-55V or AC / DC: 85-265V.
² With odd parity, even parity, no parity, 2 stop bits and other communication methods are free to set.
² Communication speed optional, the maximum communication speed to 115200 bps.
² The intelligent transducer with the smallest size and wide current measurement range in the peer.
² Electroplating has a positive and negative cumulative, and power-down storage function.
² With red and green light-emitting diode instructions function, the red light indicates the normal operation of the product (100mS flashing), the green light indicates the product communication.
² High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.