Single phase AC Voltage Tranducer

This device is a 1-phase AC voltage electrical isolation transducer. Using the principle of electromagnetic isolation, the input of the AC voltage and current signals are converted into standard analog output signal to achieve the AC voltage signal measurement and monitoring. The input and output of the product have very good linearity realation. The products are widely used in telecommunications, electricity, railways, industrial monitoring and other fields.
Data SheetTest conditions: room temperature: 25℃
Input range: voltage 0-1V~500V AC;
Output: 0-5V, 0-20mA, 0-10V, 4-20mA; 0-5KHz, 0-10KHz;
Power supply: 12V, 15V, 24V DC, 85-265V AC/DC(MS3 case);
Accuracy: 0.5;
Load capacity: ≥2KΩ (voltage output); ≤250Ω (current output);
Temperature drift: ≤200ppm/°C;
Isolation voltage: ≥2500 V DC;
Response time: ≤300 mS;
Rated power consumption: <0.5W;
Output ripple: ≤10mV
Frequency range: (45~65Hz up to 5K, please specify when ordering)
Surge immunity:
Power port level ± 0.5KV (L-N/2Ω/integrated wave)
Analog I / O port.± 0.5KV (L-N/40Ω/ integrated wave)
Impulse immunity: input / power port ± 2KV, analog I / O port ± 1KV;
Input overload capacity: Voltage: 2 times the nominal value
Operating temperature: -10 ~ 60°C; humidity: ≤95 %( no dew);
Storage temperature: -55 ~+65°C; humidity: ≤95 % (no dew).
MS1 case
MS2 case
MS3 case
Installation dimensions
Current output wiring drawing of CE-VJ03 - ** MS *
Voltage output wiring drawing of CE-VJ03 - ** MS *
Frequency output wiring drawing of CE-VJ03-F * MS *
Product voltage input port and power port have a strong anti-interference ability, can withstand 4KV and 2KV surge impact;
Input and output are isolated from each other, safe and reliable;
Rail or screw for installation,, easy and reliable.