Two input two output DC current signal isolator

HOME > Current > Standard Signal Isolator

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • The main function of the signal isolator is to isolated transmit the input DC voltage (current) signal into the standard current or voltage signal. The product contains two efficient micro power isolated power supplies that provides an isolated power supply to the pre-stage primary sensor while powering the internal signal processing circuitry. The products are widely used in analog signal isolation conversion of industrial field, such as communications, power rail, industrial control and other automation and control fields.


    Data Sheet

    Test conditions: auxiliary power: +24 V
    Input range:
    Voltage range:  75mV~300V DC,
    The first way current range: 10mA~5A DC,
    The second way current range:10mA~200mA DC;
    Output: 0-20mA, 4-20mA, 0-5V, 0-10V, 0-15V(special)
    Note: When input signal is 1-5V or 4-20mA, it is not allowed to output a negative signal,
    Please specify the requirements of "shielding negative signal" when ordering, as described in section IX.1.
    Power supply: +24VDC(-15%~+20%);   
    Power distribution output: 24VDC±3.6V/25mADC;
    Accuracy: 0.2;      
    Load capacity: current output ≤500Ω; voltage output ≥2kΩ;
    Temperature drift: ≤200ppm/℃;
    Isolation voltage: 2500VDC;   
    Response time: ≤100 mS;                
    Rated power consumption: <3W;
    Output ripple: <10mV
    Frequency response range:  none;
    Surge immunity:
    Power port three ±2KV(L-N/2Ω/ integrated wave)  
    Output port three±2KV (L-N/40Ω/ integrated wave);
    Impulse immunity:
    input/power port ± 2KV, analog I/O port ± 1KV;  
    Input overload capacity:
    2 times nominal value for the measured voltage(apply a second, repeat 10 times, interval 10S),
    20 times nominal value for the measured current apply a second, repeat 5 times, interval 300S);
    Operating temperature: -20~70℃, humidity: ≤95%(no dew);
    Storage temperature: -40~+70℃.

    116.png

    MD4-黑.jpg

    MD4 case

    D2.JPG

    DIN35 rail-mounted or screw-mounted installation

    117.png

    Fully isolated circuit structure:
    Two signal inputs are isolated from each other; two signal outputs are isolated from each other, signal input, output and auxiliary power supply are isolated from each other;
    Using electromagnetic isolation technology, stable and reliable performance;
    The output port and power port can withstand 2KV surge impact;
    The accuracy is better than 0.2;
    Provides the isolated 24V distribution power output, facilitates a sensor power supply;  
    Using 18mm thin shell guide rail installation, space utilization is high;
    Wiring using plug terminals, easy wiring and maintenance.


    Related Products

    Copyright© 2019 SHENZHEN SENSOR ELECTRONIC TECHNOLOGY CO., LTD粤ICP备05079934号-9