Single Phase Power Transducer

HOME > PRODUCT > Power

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • This product is an electrical isolation transducer of single-phase active and reactive power measurement, complete isolation between input and output signals. Through the internal switch can be switched to active and reactive power measurement, with polarity switch-over measurement function simultaneously, can offer unipolarity or bipolarity measurements, no need to distinguish direction of current for unipolarity measurement. Can be widely used in electricity, communications, railways, industrial control and other fields.

    Data Sheet

    * Auxiliary power supply: DC +11V~+28V (power consumption<60mA), AC/DC 220V;

    * Input range: Voltage AC:0~500V, current AC:0~25A(BS3 style),  AC:0~700A(ES3 style);

    * Output: 0-5V/1-5V/0-20mA/4-20mA or 2.5±2.5V/3±2V/10±10mA/12±8mA(bipolar measurement) , can be chosen arbitrarily;

    * Output ripple: <10mV;              

    * Operating condition: temperature: -20~60℃;

    * Accuracy:  class 0.5 ( adopts fiducial error);

    * Temperature drift: <200ppm/℃;     

    * Isolation voltage: DC 2500V;

    * Load capacity: voltage output≥1kΩ , current output≤300Ω;

    * Response time: ≤ 250 mS;

    * Input overload capacity: continuous overload: 120%; short-term overload: 2 times of the rated voltage input value, the application of 1 second, 20 times of the rated current input, the application of 1 second;

    * Rated power consumption: <1.5W;

    * Frequency range: 45Hz-400Hz;

    * Surge impact immunity:

       Power port two-level 1000V (L-N / 2Ω / integrated wave),

       Analog I/O port two-level 1000V (L-N / 40Ω / integrated wave);

    * Impulse immunity: none;

    * Storage ondition: -40~+70℃.


    blob.png


    ES3.jpg

    ES3 case style

    BS3-1.jpg

    BS3 case style



     blob.png

    Installation dimensions

    blob.png

    Connection diagram of C02/C03 product with DC power supply  


    blob.png

    Connection diagram of C02/C03 product with 110V/220V power supply

    True RMS measurement, the accuracy is superior to class 0.5.

    With active and reactive power measurement function simultaneously.

    No need to distinguish direction of current for unipolar measurement without sub-direction, can identify the phase automatically.

    Output 0-5V, 1-5V, 0-20mA and  4-20mA are free to choose.

    With function of unipolarity or bipolarity measurement setting option.

    Wide power supply, compatible with 12V/24V power supply.

    Built-in function switch can be set freely.