Single phase AC multi-parameter digital transducer

HOME > Multi-parameter > AC Multi-parameter Digital Transducer

  • ​ENTRIES:Part Number GuideData SheetFAQ
  • This product is a power integrated measurement of single-phase digital isolation transducer. It can measure the full-parameter of the AC circuit. Using high-precision 24-bit dedicated AD chip, the ratio dynamic range can be up to 1000: 1, the measurement parameters are voltage, current, frequency, active power, reactive power, power factor, total accumulative energy and other electrical parameters with high accuracy, good stability and high communication speed, the completely isolated processing technology is with anti-interference ability. Measurement of electrical parameters through the RS-485 digital interface output to achieve long-distance transmission, the product MODBUS protocol is complete compatible with a variety of configuration software or PLC equipment MODBUS (RTU) protocol. It can be applied to power, room monitoring, industrial measurement and other fields.


    Data Sheet

    NO,

    Item

    Date

    Unite

    Remarks

    1

    Accuracy

    0.2,0.5

    %

    0.2 for voltage and current value only

    Input range

    S3 case:500V*30A; S4 case:500V*500A;

    ES5 case:500V*700A; N1 case:500V*5A;

    DS5 case: 500V*200A


    The maximum range for each specification

    Frequency

    Frequency response: 20Hz-1KHz; Frequency   measurement: 20-600Hz



    2

    Baud rate

    115.2K, 57.6K, 38.4K, 19.2K, 9600(default)   4800, 2400, 1200

    bps

    Factory default communication format:   9600, N/8/1, address 1; S5 type up to 19.2K;

    Communication

    RS-485(twisted pair line) , RS-232C(treble   line, only for N style parts)


    RS422 optional

    Parity

    None, Even, Odd, Space



    Max. number of nodes

    64

    Node

    Only for RS-485

    Bus protection

    400W transient voltage


    ESD protection and thermosnap

    3

    A/D SPEED

    100

    mS


    4

    Working temperature

    -20~+60



    5

    Isolation voltage

    Input/output:   2500V DC for 1 min

    Input/power supply2500V   for 1 min

    Output/power supply2500V   for 1 min

     

    V

    The double isolation part numbers, their   output and power supply are grounded together, there is only between the input and output   isolation voltage

    6

    Overload

    2 x voltage span 1   sec. 10 for times with interval of 10 sec.

    10 x current span   for 1 sec. 5 times with an interval of 300 sec (only for hole thru.   parts) 


    The input outside the linear range will   result in poor accuracy

    7

    MTBF

    >30000

    hour


    8

    Auxiliary power supply

    +5V/+12V/+24V/+48V/ AC220V

    V

    220VAC,DC only for N case parts

    9

    Power consumption

    ≤250mW(+12V)≤500mW(+24V)

    mW

    Power consumption depends on power supply   to be used

    10

    Temperature drift

    ≤300

    ppm/

     (-20~+60)


    blob.png

    图片11.png

    CE-AJ1*-**BS3 Case Type 

    16.png

    CE-AJ1*-**BS3 Installation Diagram

    CE-AJ1*-**MN1 Case Type( 220 VAC Power Supply is optional)

    17.png

    CE-AJ1*-**MN1 Installation Diagram

    CE-AJ1*-**DS5 Case Type

    18.jpg

    CE-AJ1*-**DS5 Installation Diagram


    CE-AJ1*-**ES5 Case Type

    19.jpg

    CE-AJ1*-**ES5 Installation Diagram

    图片18.png

     CE-AJ11-**BS3 wiring diagram

    (Terminal 7 output is +5 V to provide 5V output (<20mA), figure 6.2 terminal 7 Vss for the 485 output.

    图片19.png

    CE-AJ12-**BS3 wiring diagram

    (Terminal 7 output is +5 V to provide 5V output (<20mA), figure 6.2 terminal 7 Vss for the 485 output.238.png

                                                             CE-AJ12-**MN1 wiring  drawing


    239.png

     Wiring diagram of S5 case


    ²   Available with wide power supply: DC: 10-30V or 10-55V

    ²  With odd parity, even parity, no parity, 2 stop bits and other communication methods are free to set.

    ²  Communication speed optional, the maximum communication speed to 115200 bps.

    ²  The intelligent transducer with the smallest size and wide current measurement range in the peer

    ²  Electroplating has a positive and negative cumulative, and power-down storage function.

    ²  With red and green light-emitting diode instructions function, the red light indicates the normal operation of the product (100mS       flashing), the green light indicates the product communication.

    ² High anti-interference ability, the input, output and power port to resist the surge voltage up to 2KV or more.


    Related Products

    Copyright© 2019 SHENZHEN SENSOR ELECTRONIC TECHNOLOGY CO., LTD粤ICP备05079934号-9